Active Power Measurement with the CR6250/60 Power Transducer

138

Applications

H

3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119

Web:

http://www.crmagnetics.com

E-mail:

sales@crmagnetics.com

The Professional

Energy Monitoring

Company

ISO 9001:2008QualityManagementSystem

M N TI

current sense points.

L1 L2 L3 N

LOAD

1

2

3

4

5

6

7

8

9

H1

H1

H1

X1

X1

X1

R

R

R

I line

A

B

C

V

L-N

N

V

L-N

The CR6250 and CR6260 series of Power Transducers gives the designer a simple and effective way to measure and

record the instantaneous power usage for 3 – phase 4 – wire loads. These devices are also known as 3 element

power transducers. All 3 current inputs are needed because 4 – wire power systems have a neutral return path,

and differences in phase currents results in neutral currents, thus requiring all phase information. Hence, these

Wye connections must be measured with 3 current sense points.

Calculation of full scale output:

Using a CR6250-500-5 for example, the unit is calibrated to output the

fullscale reading when a balanced purely resistive load is being powered by 500 Vrms line to neutral, and the

amount of current draw on each leg is 5 Arms. Power in any one leg will be the volts across the leg times the

current through the leg times the power factor. For calibration, the value of the power factor is unity (1) for a

purely resistive load. For the above diagram, the voltage across the element is V L-N, or 500Vrms. The current

is Ip, which for balanced Wye loads flows through each element. Thus, the power in one of the legs for a full

scale reading using a 500-5 unit would be 500 X 5 = 2,500 Watts. There are then 3 legs on a 3-phase line, so

the total power, full scale would be 3 X 2,500 = 7,500 Watts. The 500-5 transducer will output fullscale (5VDC

or 20mA) when the power being used is 7,500 Watts. Using this same methodology, the following simplified

formula will give the full scale reading from any Wye transducer: Part number CR6250 – AAA - BB,

Full

scale in Watts = AAA X BB X 3

.

External current transformers and voltage transformers

can be used to extend the reading range of

any transducer. Voltage and current transformers are sized according to turns ratio. A turns ratio on a current

transformer of 100:5 represents a turns ratio of 100/5 or 20. Thus for every 1 amp from the current

transformer, this represents 20 Amps in the measured line. Since power = V X I X PF (power factor), the

amount of power measured when using external current and voltage transformers will be V X I X PF X current

ratio X voltage ratio. Using our same example as before, with a CR6250-500-5, if an external current

transformer with a ratio of 20 is used, as well as an external voltage transformer with a ratio of 2, then the

new full scale output of the transducer will equal 7,500 X 20 X 2 = 300,000 Watts!!! A simplified formula for

this situation is:

Full Scale Watts = AAA X BB X 3 X CT ratio X VT ratio.

Please refer to “

Selecting

ANSI Class Metering Current Transformers”

and “

Using External Current Transformers with Other CR Devices”

for more information on transformer ratios and applying external transformers to transducers and other

devices.