One of the most important applications of the CR7310 relay is to monitor 3 phase imbalances and ground faults.

This application can help protect sensitive equipment and minimize losses from equipment failure. All three phas-

es, plus neutrals as shown, are routed through the sensor window.

3 Phase Y phase currents by definition must cancel when the loads are equal. Passing all three phases of the Y

through the sensor will normally result in zero amperage reading. When an imbalance occurs, the phases do

not cancel, and the relay trips.

This type of imbalance scheme works best due to the fact that all fault conditions, leg to leg, leg to neutral, and

leg to ground can be sensed. Sensing only neutral currents will not necessarily indicate a ground fault

condition.

Ground fault indication can only be sensed in a Delta configuration. Leg to leg imbalances are not detectable

due to the absence of a neutral return path.

The CR7310 comes standard with a mechanical relay that provides a Form C single pole contact. Other outputs

such as transistor and triac switches are available as options. Typically, the mechanical relay is used to provide

higher current switching for other motors and loads, and the solid state options are used to interface with digital

and PLC circuitry, which eliminates switch bouncing.

A latching version is available that can be used to force reset when a trip occurs. The relay, once tripped, stays

tripped regardless of current level sensed, until power is reset.