126
G
460 Voltage Transformers
The 460 Series
of Voltage transformers are designed to give
accurate measurement of low voltage systems (up to 600 VAC) by
stepping down higher voltages to 110 VAC. Useful for monitoring
and measuring incoming building or factory voltages.
H1
H2
X1
X2
31.75
1.25
56.64
2.23
101.60
4.00
120.14
4.73
LABEL
59.69
2.35
95.25
3.75
114.05
4.49
(2) BOSSES
0.38
12.70
.50
73.15
2.88
84.84
3.34
107.44
4.23
23.62
.93
(4) HOLES
10.92
.43
PART NUMBERS
Part Number
Voltage Rating
Turns Ratio
Rec. Primary
Fuse Rating
460-069
69.3:120
0.58:1
5.0
460-120
120:120
1:1
4.0
460-208
208:120
1.73:1
2.0
460-240
240:120
2:1
2.0
460-277
277:120
2.31:1
2.0
460-288
288:120
2.4:1
1.5
460-300
300:120
2.5:1
1.5
460-346
346:120
2.88:1
1.5
*
460-480
*
480:120
4:1
1.0
*
460-600
*
600:120
5:1
0.75
460
Potential Transformers
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web:
http://www.crmagnetics.comE-mail:
sales@crmagnetics.comThe Professional
Energy Monitoring
Company
ISO 9001:2008QualityManagementSystem
M N TI
E93779
LR89403
Manufactured to meet the
requirements of ANSI/IEEE C57.13
Frequency
60 Hz.
*Models designed specifically for 50 hz operations are
available with reduced performance. Contact factory for
details
Standard Secondary Voltage:
120 Volts
Use with CR Magnetics Transducers
Insulation Level:
600 Volt, 10 kV BIL full wave
Accuracy Class:
0.6 W, 1.2 X at 60 Hz.
Thermal Rating:
150 VA at 30° C . amb., 100 VA at 55°C. amb
Terminals are No. 10-32 screws with one lockwasher and
one flatwasher.
Approximate weight 7.75 lbs.
Regulatory Agencies
: